204 Actual signals and parameters
NOT SAVED Parameter changes from the control panel are not stored
into the permanent memory. To store changed parameter
values, set parameter 1607 PARAM SAVE value to
SAVE….
2
1603 PASS CODE Selects the pass code for the parameter lock (see
parameter 1602 PARAMETER LOCK).
0
0…65535 Pass code. Setting 358 opens the lock. The value reverts
back to 0 automatically.
1 = 1
1604 FAULT RESET
SEL
Selects the source for the fault reset signal. The signal
resets the drive after a fault trip if the cause of the fault no
longer exists.
KEYPAD
KEYPAD Fault reset only from the control panel 0
DI1 Reset through digital input DI1 (reset on the rising edge of
DI1) or from the control panel
1
DI2 See selection DI1.2
DI3 See selection DI1.3
DI4 See selection DI1.4
DI5 See selection DI1.5
START/STOP Reset along with the stop signal received through a digital
input, or from the control panel.
Note: Do not use this option when start, stop and direction
commands are received through fieldbus communication.
7
COMM Fieldbus interface as the source for the fault reset signal, ie
control word 0301 FB CMD WORD 1 bit 4 (with ABB drives
profile 5319 EFB PAR 19 bit 7). The control word is sent by
the fieldbus controller through the fieldbus adapter or
embedded fieldbus (Modbus) to the drive. For the control
word bits, see sections DCU communication profile on page
320 and ABB drives communication profile on page 315.
8
DI1(INV) Reset through inverted digital input DI1 (reset on the falling
edge of DI1) or from the control panel
-1
DI2(INV) See selection DI1(INV).-2
DI3(INV) See selection DI1(INV).-3
DI4(INV) See selection DI1(INV).-4
DI5(INV) See selection DI1(INV).-5
All parameters