To calculate the output current, multiply the current in the rating table with the derating factor
k, which for x meters (1000 m <= x <= 4000 m) or feet (3281 ft <= x <= 13123 ft) is:
Fuses
The tables list the fuses for protection against short circuits in the input power cable or drive.
Either fuse type can be used if it operates rapidly enough. The operating time depends on
the supply network impedance, and the cross-sectional area and length of the supply cable.
Do not use fuses with a higher current rating than that given in the table. You can use fuses
from other manufacturers, if they meet the ratings, and if the melting curve of the fuse does
not exceed the melting curve of the fuse mentioned in the table.
■ gG fuses (IEC)
Make sure that the operating time of the fuse is less than 0.5 seconds. Obey the local
regulations.
Fuses
Min. short-
circuit cur-
rent
1)
Drive in-
put cur-
rent
IEC type
ACS480-04-…
IEC
60269
size
ABB typeVoltage
rating
I
2
tNom. cur-
rent
VA
2
sAAA
3-phase U
N
= 400 V
000OFAF000H65001106484.202A7-4
000OFAF000H65001106485.303A4-4
000OFAF000H1050036010806.404A1-4
000OFAF000H1050036010809.005A7-4
000OFAF000H165007401612811.507A3-4
000OFAF000H165007401612815.009A5-4
000OFAF000H2550025002520020.212A7-4
000OFAF000H3250045003225627.2018A-4
000OFAF000H50500155005040040.0026A-4
000OFAF000H63500200006350445.0033A-4
000OFAF000H80500360008064050.0039A-4
000OFAF000H1005006500010080056.0046A-4
000OFAF000H1005006500010080060.0050A-4
1)
Minimum allowed short-circuit current of the electrical power network
■ gR fuses (IEC)
Fuses
Min. short-
circuit cur-
rent
1)
Drive in-
put cur-
rent
IEC type
ACS480-04-…
IEC
60269
size
Bussmann
type
Voltage
rating
I
2
t
Nominal
current
VA
2
sAAA
3-phase U
N
= 400 V
00170M269469012525484.202A7-4
102 Technical data