Maximum motor cable lengthFrame
ftm
Standard drive, without external options
492150R1, R2
492150R3, R4
With external output chokes
820250R1…R3
656200R4
Note: In multimotor systems, the calculated sum of all motor cable lengths must not exceed
the maximum motor cable length given in the table.
EMC compatibility and motor cable length
To comply with the EMC limits in the European EMC Directive (standard IEC/EN 61800-3),
do not exceed these maximum motor cable lengths. They are valid for 4 kHz switching
frequency.
Maximum motor cable length, 4 kHzFrame
C3C2
C1
1)
ftmftmftm
With internal EMC filter
3-phase 380…480 V
100303010--R1
66203010--R2
100303010--R3
100303010--R4
With optional external EMC filter
3-phase 208…240 V/380…480 V
150501505010030R1
150501505010030R2
150501505010030R3
150501003010030R4
1)
Category C1 with conducted emissions only. Radiated emissions are not compatible when measured with the standard
emission measurement setup and must be measured on cabinet and machine installations for each case.
Note:
• For 3-phase 380…400 V drives, the maximum motor cable lengths are according to C3
in the above table with an internal EMC filter.
Brake resistor connection data
The brake resistor output is conditionally short-circuit proof by IEC/EN 61800-5-1
and UL 61800-5-1.
Short-circuit protection
(IEC 61800-5-1,
IEC 60439-1, UL 61800-5-
1)
Rated conditional short-circuit current is as defined in IEC 60439-1.
Technical data 113