Protection classes
IP20. The drive must be installed in a cabinet to fulfill the requirements for shielding
from contact.
Degree of protection
(IEC/EN 60529)
UL Open Type. For indoor use only. UL type 1 kit is available as an option.Enclosure types
(UL 61800-5-1)
lllOvervoltage category
(IEC 60664-1)
lProtective classes
(IEC/EN 61800-5-1)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated indoor
controlled environment.
Transportation in the
protective package
Storage in the protective
package
Operation installed for
stationary use
Requirement
--400/480 V units:
0…4000 m above sea level
(with derating above
1000 m)
Installation site altitude
See Output derat-
ing (page 98).
-40…+70 °C ±2%-40…+70 °C ±2%-10…+60 °C (14…140 °F).Air temperature
(-40…+158 °F ±2%)(-40…+158 °F ±2%)
Output is derated above
50 °C (122 °F). See Output
derating (page 98).
No frost allowed.
Max. 95%Max. 95%5…95%Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
of corrosive gases.
IEC 60721-3-2: 1997IEC 60721-3-1: 1997IEC 60721-3-3: 2002Contamination levels
(IEC 60721-3-x)
Class 2C2Class 1C2Class 3C2- Chemical gases
Class 2S2Class 1S3. (packing must
support this, otherwise
1S2)
Class 3S2. No conductive
dust allowed.
- Solid particles
--Pollution degree 2Pollution degree
(IEC/EN 61800-5-1)
--frequency 10…150 Hz;Sinusoidal vibration
amplitude ±0.075 mm
(0.003 in), 10…57,56 Hz;
(IEC 60068-2-6, Test Fc
2007-12)
constant peak acceleration
10 m/s2 (33 ft/s2),
57,56…150 Hz; sweep:
1 oct/min;
10 sweep cycles in each
axis with STO active;
uncertainty ±5.0%;
normal mounting
Technical data 115