UL (NEC) ratings
FrameOutput ratingsInput currentUL (NEC) type
ACS480-04-…
Heavy-duty useLight-duty useNominal useMax. cur-
rent
with
choke
No choke
P
Hd
I
Hd
P
Ld
I
Ld
P
N
I
N
I
max
I
1
I
1
hpAhpAhpAAAA
3-phase U
N
= 480 V, 60 Hz
R10.751.61.02.11.02.12.92.13.402A1-4
R11.02.11.53.01.53.03.83.04.803A0-4
R11.53.02.03.52.03.55.43.55.603A5-4
R12.03.42.04.83.04.86.14.87.704A8-4
R12.04.03.06.03.06.07.26.09.606A0-4
R13.04.85.07.65.07.68.67.612.207A6-4
R25.07.67.511.07.511.013.711.017.6011A-4
R37.511.010.014.010.014.019.814.022.4014A-4
R310.014.015.021.015.021.025.221.033.6021A-4
R415.012.020.027.020.027.037.827.037.9027A-4
R420.027.025.034.025.034.048.634.044.7034A-4
R430.040.030.042.030.042.072.042.050.4042A-4
See Notes and definitions (page 98).