Typical power cable sizes
These are the typical power cable (and conductor) sizes at the nominal drive current.
Frame
Cable conductor sizes (mm
2
)
1)
IEC type
ACS480-04-…
3-phase U
N
= 400 V
R13×1.5 + 1.502A7-4
R13×1.5 + 1.503A4-4
R13×1.5 + 1.504A1-4
R13×1.5 + 1.505A7-4
R13×1.5 + 1.507A3-4
R13×2.5 + 2.509A5-4
R23×2.5 + 2.512A7-4
R33×6 + 6018A-4
R33×6 + 6026A-4
R43×10 + 10033A-4
R43×16 + 16039A-4
R43×25 + 16046A-4
R43×25 + 16050A-4
1)
Size of typical power cable (symmetrical, shielded, three-phase copper cable). Note that for the input power connection,
you may have to use two separate PE conductors (IEC 61800-5-1).
FrameWire size, Cu (AWG)UL (NEC) type
ACS480-04-…
3-phase U
N
= 480 V
R11602A1-4
R11603A0-4
R11603A5-4
R11604A8-4
R11606A0-4
R11407A6-4
R214011A-4
R310014A-4
R310021A-4
R48027A-4
R46034A-4
R44042A-4
Terminal data for the control cables
This table shows the control cable terminal data of the standard drive variant, that is, the
base unit with RIIO-01 I/O & EIA-485 module.
TorqueWire size
lbf·inN·mAWGmm
2
4.4…5.30.5…0.626…160.14…1.5
110 Technical data