Maximum cable lengths:
300 m (1000 ft) between activation switch [K] and drive control unit
60 m (200 ft) between multiple drives or inverter units
60 m (200 ft) between external power supply and first control unit
Note: A short-circuit in the wiring between the switch and an STO terminal causes a
dangerous fault. Therefore, it is recommended to use a safety relay (including wiring
diagnostics) or a wiring method (shield grounding, channel separation) which reduces or
eliminates the risk caused by the short-circuit.
Note: The voltage at the STO input terminals of the drive must be at least 13 V DC to be
interpreted as “1”.
The pulse tolerance of the input channels is 1 ms.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control unit at
the control unit only.
Ground the shield in the cabling between two control units at one control unit only.
154 The Safe torque off function