10. Connect the PE conductors of the input power cable to the grounding terminal. Tighten
to torque 1.2 N·m (10.6 lbf·in).
11. Connect the phase conductors of the input power cable to the L1, L2 and L3 input
terminals. Tighten to torque 0.5 N·m (5 lbf·in).
12. Mechanically attach all of the cables on the outside of the drive.
Connecting the control cables
Before you connect the control cables, make sure that all option modules are installed.
Default I/O connection diagrams (ABB standard macro)
The connection diagrams below are valid for the standard drive variant, ie, drive equipped
with the RIIO-01 I/O & EIA-485 module. ABB standard macro (parameter 96.04) is in use
with the default parameter settings.
2)
Description
Term.
1)
Connection
Analog inputs and outputs
Signal cable shield (screen)SCR
SCR
AI1
AGND
+10 V
AI2
AGND
AO1
AO2
AGND
1…10 kohm
Max. 500 ohm
Output frequency: 0...10 VAI1
Analog input circuit commonAGND
Reference voltage 10 V DC+10V
Not configuredAI2
Analog input circuit commonAGND
Output frequency: 0...20 mAAO1
Motor current: 0...20 mAAO2
Analog output circuit commonAGND