Make sure that the cooling air exhaust at the top of the drive is not below the cooling
air inlet at the bottom of the drive.
Make sure that the hot exhaust air from a drive does not flow into the cooling inlet of
other drives or equipment.
Drives equipped with the optional UL type 1 kits: If you install the drives side-by-side,
make sure that their air outlets do not face each other.
Examining the installation site
Examine the installation site:
The installation site is sufficiently ventilated or cooled to remove heat from the drive.
See the technical data.
The ambient conditions of the drive meet the specifications. See the technical data.
The wall behind the unit and the material above and below the unit is of non-flammable
material.
The installation surface is as close to vertical as possible and strong enough to support
the drive.
There is enough free space around the drive to enable cooling, maintenance, and
operation. See the free space specifications for the drive.
Make sure that there are no sources of strong magnetic fields such as high-current
single-core conductors or contactor coils near the drive. A strong magnetic field can
cause interference or inaccuracy in the operation of the drive.
Required tools
To install the drive mechanically, you need the following tools:
a drill and suitable drill bits
a screwdriver or wrench with a set of suitable bits (PH0–3, PZ0–3, T15–40, S4–7) (For
motor cable terminals, the recommended shaft length is 150 mm (5.9 in))
a tape measure and spirit level
personal protective equipment.
Unpacking the delivery
Make sure that all of the items are present and that there are no signs of damage.
Standard drive package contents:
Drive
Assistant control panel (not installed)
I/O & EIA-485 module RIIO-01 (not installed)
Mounting template (for R3 and larger drives)
Installation accessories (cable clamps, etc.)
Options, if ordered with a plus code. Note that if a fieldbus adapter is ordered, it replaces
the I/O & EIA-485 module RIIO-01 of the standard delivery.
Multilingual warning sticker sheet (residual voltage warning)
Safety instructions
Quick installation and start-up guide
Hardware and firmware manuals, if ordered with a plus code.
36 Mechanical installation