DescriptionTerminalConnection
×Auxiliary voltage output +24 V DC, max. 250 mA+24 V
OUT1
SGND
IN1
IN2
+24 V
DGND
DCOM
DI1
DI2
+24 V
DGND
DCOM
DI1
DI2
AI1
+10V
GND
SCR
DI3
DI4
DI5
DIO1
×Auxiliary voltage output commonDGND
×Digital input common for allDCOM
×Stop (0) / Start (1)DI1
×Forward (0) / Reverse (1)DI2
Constant frequency/speed selectionDI3
Constant frequency/speed selectionDI4
Ramp set 1 (0) / Ramp set 2 (1)DI5
Not configuredDIO1
Output frequency/speed ref: 0…10 V DCAI1
Reference voltage +10 V DC (max. 10 mA)+10V
Analog circuit common / DO commonGND
Signal cable shieldSCR
×Safe torque off. Both IN1 AND IN2 circuits must be closed
for the drive to start. (Factory connection.)
SGND
×IN1
×IN2
×OUT1
Start-up
The BIO-01 module is automatically identified by the drive firmware. To configure the inputs,
refer to the drive firmware manual.
Technical data
Control connection data: Spring type terminal blocks. Conductor size accepted by the
terminals: 0.2…1.5 mm
2
(24…16 AWG). Exception: max. 0.75 mm
2
(18 AWG) for a
multistranded conductor with a ferrule and plastic sleeve.
Internal connections of GND and SCR terminals:
OUT1
SGND
IN1
IN2
+24 V
DGND
DCOM
DI1
DI2
+24 V
DGND
DCOM
DI1
DI2
AI1
+10V
GND
SCR
DI3
DI4
DI5
DIO1
BIO-01 I/O extension module 171