2
2
6
7
5
4
Note: If you have the BIO-01 option module, you can add one additional fieldbus module
on top of it.
Installing a side option
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death, or
damage to the equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
1.
Stop the drive and do the steps in section Electrical safety precautions (page 14) before
you start the work.
2. Remove the two screws from the front-most grounding clamp at the bottom of the drive.
3. Carefully align the side option with the connectors on the right side of the drive.
4. Fully push the option module into position.
5. Tighten the locking screw of the option module.
Electrical installation IEC 67