■ Connection diagram
PE
L1 L2 L3 R-
UDC+
R+
T1/U T2/V T3/W
U1 W1
3 ~ M
V1
PE
L1 L2 L3PE
562
4
1
3
Supply disconnecting device and fuses1.
Input power wiring2.
Enclosure that drive is installed in3.
Protective earth (PE) conductor(s). According to drive safety standard IEC/EN 61800-5-1:4.
• there must be two separate PE conductors, or one min. 8 AWG (10 mm
2
) Cu conductor
• minimum size for individual PE conductor is 14 AWG (2.5 mm
2
) Cu.
Motor wiring5.
Brake resistor wiring (optional)6.
■ Connection procedure
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death, or
damage to the equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
1.
Stop the drive and do the steps in section Electrical safety precautions (page 14) before
you start the work.
2. Install the conduits, and attach them to the cable entry plate of the enclosure that the
drive is installed in.
3. Make sure of a proper grounding of the conduit at the cable entry.
4. Strip the conductor ends and pull the conductors through the conduits.
5. Open the locking screw of the front cover and lift the front cover up.
Electrical installation – North America 75