Technical data 119
Electrical power network specification
Voltage (U
1
) ACS530-04-xxxx-4 drive modules: 380…480 V AC 3-phase ± 10%. This is
indicated in the type designation label as typical input voltage levels
3 400/480 V AC.
Network type TN (grounded) and IT (ungrounded) systems
Rated conditional short-
circuit current I
cc
(IEC
61800-5-1)
Maximum allowable prospective short-circuit current is 65 kA when protected
by the fuses given in the fuse table.
Short-circuit current
protection (UL 508A)
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when by the fuses
given in the fuse table.
Frequency 48 to 63 Hz, maximum rate of change 17%/s
Imbalance Max. ± 3% of nominal phase to phase input voltage
Fundamental power factor
(cos phi
1
)
0.98 (at nominal load)
Motor connection data
Motor types Asynchronous AC induction motor
Voltage (U
2
) 0 to U
1
, 3-phase symmetrical. This is indicated in the type designation label
as typical output voltage level 3 0…U
1
,
Frequency 0.…500 Hz
Frequency resolution 0.01 Hz
Current See section Ratings.
Frequency 0…500 Hz. For drives with du/dt filter:
200 Hz
Switching frequency = nominal switching frequency. Minimum switching frequency 1.5 kHz, 2 kHz,
4 kHz, 8 kHz (depends on the parameter settings)
Maximum recommended
motor cable length
Vector control
300 m (984 ft)
Note: Motor cable longer than 100 m (328 ft) is allowed but then the EMC
Directive requirements of Category C3 may not be fulfilled.
DC connection data
Drive type I
DC
(A) Capacitance (mF)
U
N
= 400 V
ACS530-04-505A-4 640 14
ACS530-04-585A-4 714 14
ACS530-04-650A-4 870 14
ACS530-04-725A-4 909 21
ACS530-04-820A-4 1033 21
ACS530-04-880A-4 1120 21
Control unit (CCU-24) connection data
External power supply
Term. 40, 41
Maximum power: 36 W, 1.50 A at 24 V AC/DC ±10% as standard
Terminal size: 0.14…2.5 mm
2
+24 V DC output
(Term. 10)
Total load capacity of this output is 6.0 W (250 mA / 24 V) minus the power
taken by the option modules installed on the board.
Terminal size: 0.14…2.5 mm