Safe torque off function 141
Activation switch
In the wiring diagrams below, the activation switch has the designation [K]. This represents
a component such as a manually operated switch, an emergency stop push button switch,
or the contacts of a safety relay or safety PLC.
In case a manually operated activation switch is used, the switch must be of a type
that can be locked out to the open position.
The contacts of the switch or relay must open/close within 200 ms of each other.
An CPTC-02 thermistor protection module can also be used. For more information,
see section CPTC-02 ATEX-certified thermistor protection module, (external
24 V AC/DC and isolated PTC interface) on page 172.
Cable types and lengths
Double-shielded twisted-pair cable is recommended.
Maximum cable lengths:
300 m (1000 ft) between activation switch [K] and drive control unit
60 m (200 ft) between multiple drives
60 m (200 ft) between external power supply and first drive.
Note: The voltage at the INx terminals of each control unit must be at least 17 V DC to be
interpreted as “1”.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
Ground the shield in the cabling between two control units at one control unit only.
Single drive (internal power supply)
OUT2
OUT1
+ 24 V DC
IN1
IN2
T1/U,
T2/V,
T3/W
Control unit
SGND
+ 24 V DC
STO
UDC+
UDC-
A
Drive
34
35
36
37
38
Control logic
K