Installation instructions 79
Connecting the power cables
Connection diagram
1 For alternatives, see section Selecting the supply disconnecting device on page 52. In the installing
example of this chapter, the disconnecting device is not in the same cubicle with the drive module.
2 If a shielded cable is used (not required but recommended) and the conductivity of the shield is
< 50% of the conductivity of the phase conductor, use a separate PE cable (2a) or a cable with a
grounding conductor (2b).
3 We recommend 360-degree grounding at the cabinet entry if a shielded cable is used. Ground the
other end of the input cable shield or PE conductor at the distribution board.
4 We recommend 360-degree grounding at the cabinet entry, see page 42.