Introduction to the manual   23
Categorization by frame size and option code
The instructions, technical data and dimension drawings which concern only certain drive 
frame sizes are marked with the symbol of the frame size (R10 or R11). The frame size is 
marked on the type designation label.
The instructions and technical data which concern only certain optional selections are 
marked with option codes, eg, +J410. The options included in the drive can be identified 
from the option codes visible on the type designation label. The option selections are listed 
in section Type designation key on page 34. 
Quick installation, commissioning and operating 
flowchart
Task See
Plan the mechanical and electrical installation and acquire 
the accessories needed (cables, fuses, etc.).
Check the ambient conditions, ratings, required cooling air 
flow, input power connection, compatibility of the motor, 
motor connection, and other technical data.
Guidelines for planning the cabinet installation 
(page 37)
Guidelines for planning the electrical installation 
(page 51)
Technical data (page 115)
Option manual (if optional equipment is 
included)
Unpack and check the units. 
Check that all necessary optional modules and equipment 
are present and correct.
Only intact units can be started up.
Moving and unpacking the unit (page 70)
Checking the delivery (page 74)
If the drive module has been non-operational 
for more than one year, the converter DC link 
capacitors need to be reformed. (Reforming the 
capacitors, page 111)
Check the installation site. Attach the base of the cabinet to 
the floor.
Checking the installation site (page 69)
Ambient conditions (page 122)
Guidelines for planning the cabinet installation 
(page 37)
Route the cables. Routing the cables (page 60)
Check the insulation of the supply cable, the motor and the 
motor cable. 
Checking the insulation of the assembly (page 
75)