Safe torque off function 143
Single-channel connection
Wiring examples
An example of a Safe torque off wiring with internal +24 V DC power supply is shown
below.
+24 V
OUT1
SGND
IN2
K
IN1
Drive
Control unit
Notes:
Both STO inputs (IN1, IN2) must be connected to the activation switch. Otherwise, no SIL/PL
classification is given.
Pay special attention to avoiding any potential failure modes for the wiring. For example, use shielded
cable. For measures for fault exclusion of wiring, see eg. EN ISO 13849-2:2012, table D.4.
2414
2313 Y1
A2
Y2
A1
31
32
Safety relay
Safe PLC
OUT
GND
34
37
35
38
Drive
36 SGND
IN1
IN2
OUT1
OUT2
K

Table of Contents