450 Fieldbus control through the embedded fieldbus interface (EFB)
14 REQ_LOCAL_LO
CK
1 Drive does not switch to local control mode (see
parameter 19.17 Local control disable).
0 Drive can switch between local and remote control
modes.
15 Reserved
16 FB_LOCAL_CTL 1 Local mode for control from the fieldbus is requested.
Steal control from the active source.
0(no op)
17 FB_LOCAL_REF 1 Local mode for reference from the fieldbus is requested.
Steal reference from the active source.
0(no op)
18 Reserved for
RUN_DISABLE_1
Not yet implemented.
19 Reserved
20 Reserved
21 Reserved
22 USER_0 Writable control bits that can be combined with drive logic
for application-specific functionality.
23 USER_1
24 USER_2
25 USER_3
26…
31
Reserved
Bit Name Value State/Description