96 Program features
A user parameter set contains all editable values in parameter groups 10…99 except
• forced I/O values such as parameters 10.03 DI force selection and 10.04 DI
forced data
• I/O extension module settings (group 15)
• data storage parameters (group 47)
• fieldbus communication settings (groups 50…53 and 58)
• parameter 95.01 Supply voltage.
As the motor settings are included in the user parameter sets, make sure the settings
correspond to the motor used in the application before recalling a user set. In an
application where different motors are used with the drive, the motor ID run needs to
be performed with each motor and the results saved to different user sets. The
appropriate set can then be recalled when the motor is switched.
Settings
Parameters 96.10…96.13 (page 357).
Data storage parameters
Twelve (eight 32-bit, four 16-bit) parameters are reserved for data storage. These
parameters are unconnected by default and can be used for linking, testing and
commissioning purposes. They can be written to and read from using other
parameters’ source or target selections.
Settings
Parameter group 47 Data storage (page 322).
User lock
For better cyber security, it is highly recommended that you set a master pass code to
prevent changing of parameter values and/or the loading of firmware and other files.
WARNING! ABB will not be liable for damages or losses caused by the failure
to activate the user lock using a new pass code. See Cyber security disclaimer
(page 17).
To activate the user lock for the first time, enter the default pass code, 10000000, into
96.02 Pass code. This will make parameters 96.100…96.102 visible. Then enter a
new pass code into 96.100 Change user pass code, and confirm the code in 96.101
Confirm user pass code. In 96.102 User lock functionality, define the actions that you
want to prevent (we recommend you select all the actions unless otherwise required
by the application).