EasyManua.ls Logo

ABB ACS560 - Page 98

ABB ACS560
514 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
98 Program features
Example of using dead-band in AI1
If,
12.110 AI dead band = 5%
12.15 AI1 unit selection = V
12.18 AI1 max = 10 V
then,
AI dead-band value = 10 * 5% = 0.5 V
AI Hysteresis value = 0.5 * 10% = 0.05 V
Hysteresis negative value = 0.5 - 0.05 = 0.45 V
Hysteresis positive value = 0.5 + 0.05 = 0.55 V
When AI1 input voltage increases, up to 0.55 V, the AI1 actual value (12.11) displays
zero. After AI1 input voltage reaches 0.55 V, the AI1 actual value displays 0.55 V and
continues to display the detected value up to 10 V (12.18).
When AI1 input voltage decreases, the AI1 actual value displays the detected value
up to 0.45 V. From 0.45 V to zero, the AI1 actual value displays Zero.
See the timing diagram below:
Dead-band function timing diagram
Settings
Parameter 12.110 AI dead band (page 193)
12.11 AI1 actual value
12.18 AI1 max (V)
12.18 AI1 max (V)
AI input reference
a
0.5
0.55
a - Dead-band value
b - Hysteresis negative value
c - Hysteresis positive value
0.45
b
c

Table of Contents

Other manuals for ABB ACS560

Related product manuals