5. Remove the rubber grommets of the cables to be installed from the cable entry
plate. Install the grommets downwards also in unused holes.
6. Attach the cable conduits to the conduit plate. Make sure the conduit is correctly
bonded at both ends and that conductivity is consistent throughout the conduit. Slide
the cables through the conduit.
7. Cut the cables to suitable length (note the extra length of the grounding conductors).
If you use a symmetrically shielded VFD cable, twist the grounding wires together
with the cable shield and connect them to the grounding terminals. Ground the
shield 360 degrees at the clamp. If you use discrete conductors connect the insulated
ground conductor to the grounding terminal.
EMT
118 Electrical installation North America (NEC)