Tightening torque for R3
1.7 N·m (1.25 lbf·ft), for R6
and R8 2 N·m (1.48 lbf·ft)
8. Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W
terminals and the phase conductors of the input cable to the L1, L2 and L3
terminals.
•
•
For frame R8: Install the common mode filter. For instructions, see Common
mode filter kit for ACS880-01 frame R7, and for ACS880-11, ACS880-31,
ACH580-31 and ACQ580-31 frame R8 (option +E208) installation instructions
(3AXD50000015179 [English]).
• If DC cables are present, use only two phase conductors and the ground
conductor. Connect the phase conductors to the UDC+ and UDC- terminals.
• Tighten the screws to the torque given in the installation drawing below.
Electrical installation – North America (NEC) 119