EasyManua.ls Logo

ABB COMMANDER C355 - Page 101

ABB COMMANDER C355
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
99
8888
OFF.3
E.05
8888
SPN.3
E.06
0.0
100.3
0.0
100.3
NO
C.CAL
E.07
NO
O.CAL
E.08
E.09
E.10
FCAL
30
r.trV
rEF
2700
F.CAL
AUtO
rEF
2700
r.trV
30
Fb.LO
100
NO
AUtO
MAN
•1
•1
•1
•1
E.05...E.10
5 CONFIGURATION MODE
•1 Displayed only if Motorized Valve with feedback output type is selected – see Section 5.2, Basic Configuration.
Analog Input 3 Offset Calibration
Analog Input 3 Value in Engineering Units
Offset [In engineering Units]
If the
and keys are not operated for three seconds the display
reverts to the offset value only.
Analog Input 3 Span Calibration
Analog Input 3 Value in Engineering Units
Span Adjustment
[0.750 to 1.250]
If the
and keys are not operated for three seconds the display
reverts to the offset value only.
Position Feedback Calibration
Select the calibration required.
NO No Calibration
AUtO Auto Calibration
_AN Manual Calibration
Regulator Travel Time
[0 to 5000 seconds]
Ensure that the value entered is compatible with the regulator motor, as
this is used to determine the length of travel of the feedback mechanism.
Motorized Valve Feedback Fully-closed Position
NO No action
YES Fully closes the valve automatically and sets the electrical
input to low range value.
Note. Input value flashes when calibration is in progress.
Motorized Valve Feedback Fully-open Position
NO No action
NO Fully opens the valve automatically and sets the electrical input
to high range value.
Note. Input value flashes when calibration is in progress.
Continued in Cold Junction Reference Value frame.
5.10 Level E Calibration

Table of Contents

Related product manuals