46
…3 PROFILES
3.2.6 Time Events – Fig. 3.7
Each state generates a source ('tEV.1' to ''tEV.4') which can be assigned to relays, digital outputs, logic
equations etc. in the same way as any other digital signal.
Time event states are provided in addition to program and segment events states and do not affect their operation.
Each segment has an associated '
EV.Nt' setting which is used to control the Time-event states.
Temperature
Time
Vent
Period
Air (event 3)
Raise to
Cook
Temp
Cook Period Cook
Time
Ext
Cool
Period
End of
Cycle
Purge and Vent (event 1)
All events switched off when
program complete
12--
EV.Nt
-2--
EV.Nt
-2-4
EV.Nt
-2--
EV.Nt
--34
EV.Nt
Water (event 4)
Steam (event 2)
Fig 3.7 Time Events
3.2.7 End of Profile State
The end of profile state is a digital source which can be assigned in the same manner as any other digital signal.
The state is set automatically when the program is complete and remains set until a reset signal is received. The
state can be configured to reset via a digital source or to reset automatically after two seconds – see Section 3.4/
Profile Control/ End of Profile Reset Source.