5.6 Level A Control Configuration A.18...A.22
5 CONFIGURATION MODE
Auto Mode Selection Source
Select the digital source used to activate auto mode.
See Rear Fold-out/ Table C
– Digital Sources.
Tune Parameter Source 1 (Gain Scheduling)
Determine the digital source used to select the proportional 1 and
integral 1 terms as the tuning parameters.
See Rear Fold-out/ Table C
– Digital Sources.
Tune Parameter Source 2 (Gain Scheduling)
Determine the digital source used to select the proportional 2 and
integral 2 terms as the tuning parameters.
See Rear Fold-out/ Table C
– Digital Sources.
Tune Parameter Source 3 (Gain Scheduling)
Determine the digital source used to select the proportional 3 and
integral 3 terms as the tuning parameters..
See Rear Fold-out/ Table C
– Digital Sources.
Tune Parameter Source 4 (Gain Scheduling)
Determine the digital source used to select the proportional 4 and
integral 4 terms as the tuning parameters.
See Rear Fold-out/ Table C
– Digital Sources.
Return to top of page.
OFF
A.5rC
A.18
OFF
t4.Sr
A...22
OFF
t3.5r
A...21
OFF
t2.Sr
A..20
OFF
t1.Sr
A.19
•2
•2
•2
•2
LEVA
CNtL
Select Pb-1 and IAt.1
Manual
•1Auto
•1
Select Pb-2 and IAt.2
•1
Select Pb-3 and IAt.3
•1
Select Pb-4 and IAt4
•1
•1 Digital inputs are active when a volt-free contact is closed or a low TTL signal is applied.
•2 PB–x and IAt.x values are set in Level 2 – see Section 3.2, Tune/Proportional Band x and Integral Action
Time x. This function is not available with Cascade control and it is not applicable to Auto/Manual Station,
Indicator or Ratio Station templates.