NV Error Opt Bd 1
Failure of non-volatile memory on option board 1 or
permanent corruption of its data.
Check calibration of AIN1 and AIN2.
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service organization.
F210.019
NV Error Opt Bd 2
Failure of non-volatile memory on option board 2 or
permanent corruption of its data.
Check calibration of AIN3 and AIN4.
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service organization.
F208.020
NV Error
Comm Bd
Failure of non-volatile memory on communications board
or permanent corruption of its data.
Acknowledge error. Check communications board is
correctly identified by device.
If problem persists contact local service organization.
F206.021
NV Error SW
Key 1
Failure of non-volatile memory on Software key 1 or
permanent corruption of its data.
Acknowledge error.
Check software key functionality is enabled.
If problem persists contact local service organization.
F204.022
NV Error SW
Key 2
Failure of non-volatile memory on Software key 1 or
permanent corruption of its data.
Acknowledge error.
Check software key functionality is enabled.
If problem persists contact local service organization.