ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 107
Delay (DELAY)
Values received are forwarded after a defined delay.
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
Any
E
Input
Always
2 4 bytes signed D Delay Parametrizable
Value in seconds;
according to KNX DPT
13.100
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
Any
A
Output
Always
Parameters
Name
Value
Visible
Description
Delay
Checkbox
Always
Enables input D (Delay)
hh:mm:ss Default value:
00:00:00
If the checkbox is
cleared
Parameter and socket
according to KNX DPT
13.100.
Range from 00:00:00 to
99:59:59.
Values outside the range
are set to the minimum or
maximum value
respectively.
If the Delay checkbox is selected, the time value field is not visible.
Function
If a new value is received during the delay, the delay restarts and the old value is discarded.
The timer resets to zero and restarts (retrigger).
Once the delay has elapsed, the output is updated to the last input value.
On enabling the delay using the checkbox, note the following:
If input D is not connected, the delay will automatically be set to 0.