ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 107
Delay (DELAY)
Values received are forwarded after a defined delay.
Inputs
2 4 bytes signed D Delay Parametrizable
according to KNX DPT
Outputs
Parameters
hh:mm:ss Default value:
00:00:00
If the checkbox is
cleared
according to KNX DPT
13.100.
Range from 00:00:00 to
99:59:59.
Values outside the range
are set to the minimum or
maximum value
If the Delay checkbox is selected, the time value field is not visible.
Function
If a new value is received during the delay, the delay restarts and the old value is discarded.
The timer resets to zero and restarts (retrigger).
Once the delay has elapsed, the output is updated to the last input value.
On enabling the delay using the checkbox, note the following:
• If input D is not connected, the delay will automatically be set to 0.