EasyManuals Logo

ABB i-bus KNX AC/S 1.x.1 Series User Manual

ABB i-bus KNX AC/S 1.x.1 Series
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #198 background imageLoading...
Page #198 background image
ABB i-bus
®
KNX
Parameters
198 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Data type
CO2 value DPT 9.008
The module has this output socket if the
Yes
option is selected for the
CO2 value
parameter.
Outputs the air quality (CO
2
)
Signal value:
0…670760 ppm
Fan coil unit, valve heating
DPT 5.001
The module has this output socket if the 2-pipe heating option or the 4-pipe heating + cooling option is selected for the Fan
coil unit parameter.
Outputs the valve position (control value) on the fan coil unit for heating.
Signal value:
0…100%
Fan coil unit, valve cooling DPT 5.001
The module has this output socket if the 2-pipe cooling option or the 4-pipe heating + cooling option is selected for the Fan coil
unit parameter.
Outputs the valve position (control value) on the fan coil unit for cooling.
Signal value: 0…100%
Fan coil unit, valve
DPT 5.001
The module has this output socket if the 2-pipe heating/cooling option is selected for the Fan coil unit parameter.
Outputs the valve position (control value) on the fan coil unit. This is for either heating or cooling depending on the
heating/cooling operating type.
Signal value:
0…100%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals