ABB i-bus
®
KNX
Parameters
198 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Data type
CO2 value DPT 9.008
The module has this output socket if the
Yes
option is selected for the
CO2 value
parameter.
Outputs the air quality (CO
2
)
Signal value:
0…670760 ppm
Fan coil unit, valve heating
DPT 5.001
The module has this output socket if the 2-pipe heating option or the 4-pipe heating + cooling option is selected for the Fan
coil unit parameter.
Outputs the valve position (control value) on the fan coil unit for heating.
Signal value:
0…100%
Fan coil unit, valve cooling DPT 5.001
The module has this output socket if the 2-pipe cooling option or the 4-pipe heating + cooling option is selected for the Fan coil
unit parameter.
Outputs the valve position (control value) on the fan coil unit for cooling.
Signal value: 0…100%
Fan coil unit, valve
DPT 5.001
The module has this output socket if the 2-pipe heating/cooling option is selected for the Fan coil unit parameter.
Outputs the valve position (control value) on the fan coil unit. This is for either heating or cooling depending on the
heating/cooling operating type.
Signal value:
0…100%