200 2CDC508198D0211 Rev. A | AC/S 1.x.1
Fan coil unit, fan manual DPT 1.011
The module has this output socket if any option except
None
Fan coil unit
Outputs whether the current fan speed has been adjusted manually by a user or it was calculated automatically by the room
thermostat.
Signal value: 0 = Automatic
1 = Manual
Fan coil unit, dew point sensor
The module has this output socket if any option except None is selected for the Fan coil unit parameter and the Yes option is
selected for the Fan coil unit, dew point sensor parameter.
Outputs the signal value from the dew point sensor in the fan coil unit.
1 = On
Fan coil unit, level sensor
The module has this output socket if any option except None is selected for the Fan coil unit parameter and the Yes option is
selected for the Fan coil unit, level sensor parameter.
Outputs the signal value from the level sensor in the fan coil unit.
Signal value: 0 = Off
1 = On
DPT 5.001
The data point type for the output socket is dependent on the settings in the module.
• If the On/Off option is selected for the Radiator parameter:
DPT 1.001
Signal value: 0 = Off, 1 = On
• If the 0…100 % option is selected for the Radiator
parameter:
DPT 5.001
Signal value: 0…100 %
Outputs the position of the radiator valve.