ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 209
separately)
Output: Operating mode normal (slave)
DPT 20.102
The module has this group object if the Display+set (slave) option is selected for the Operating mode parameter.
This group object is used for synchronization of the operating mode between the Room ASM (slave) and the room thermostat
(master). For this purpose the group object must be connected to the controller's (master's) group object of the same name.
The Room ASM sends the operating mode to the controller in this group object.
Telegram value: 0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
Input: Operating mode override (slave) Room 1 byte
DPT 20.102
C, W, T, U
The module has this group object if the
Display+set (slave)
option is selected for the
Operating mode
This group object is used for synchronization of the overridden operating mode between the Room ASM (slave) and the room
thermostat (master). For this purpose the group object must be connected to the controller's (master's) group object of the
same name.
The Room ASM receives the current overridden operating mode from the controller in this group object.
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
DPT 1.019
The module has this group object if the
Yes
option is selected for the
Window status
Input for the connection of the window status.
Telegram value: 0 = Closed
1 = Open