ABB i-bus
®
KNX
Parameters
210 2CDC508198D0211 Rev. A | AC/S 1.x.1
separately)
DPT 1.018
The module has this group object if the Yes option is selected for the Presence detector parameter.
Input for the connection of the presence status, e.g. from a presence detector.
Telegram value: 0 = Not occupied
1 = Occupied
Input: Rel. humidity Room 1 byte
DPT 5.001
C, W, T, U
The module has this group object if the Yes option is selected for the Rel. humidity parameter.
Input for the connection of the relative humidity from the sensor.
Input: CO2 value Room 2 bytes
DPT 9.008
C, W, T, U
The module has this group object if the Yes option is selected for the CO2 value parameter.
Input for the connection of the CO
2
value from the air quality sensor.
Input: Fan coil unit, valve heating
DPT 5.001
The module has this group object if the 2-pipe heating option or the 4-pipe heating + cooling option is selected for the Fan coil
unit parameter.
Input for the valve position (control value) on the fan coil unit for heating.
Telegram value: 0…100%