AC/S 1.x.1 | 2CDC508198D0211 Rev. A 221
Object name
Object type
Unit
COV send
condition
Room: CO2 value
Analog value
ppm (96)
1.0
The module has this BACnet output object if the Yes option is selected for the CO2 value parameter.
Outputs the air quality (CO
2
)
Signal value: 0…670760
Room: Fan coil unit, valve heating
Analog value
% (98)
1.0
The module has this BACnet output object if the
2-pipe heating
option or the
4-pipe heating + cooling
option is selected for the
Fan coil unit parameter.
Outputs the valve position (control value) on the fan coil unit for heating.
Signal value: 0…100%
Room: Fan coil unit, valve cooling
Analog value
% (98)
1.0
The module has this BACnet output object if the 2-pipe cooling option or the 4-pipe heating + cooling option is selected for the
Fan coil unit parameter.
Outputs the valve position (control value) on the fan coil unit for cooling.
Signal value: 0…100%
Room: Fan coil unit, valve
Analog value
% (98)
1.0
The module has this BACnet output object if the 2-pipe heating/cooling option is selected for the Fan coil unit parameter.
Outputs the valve position (control value) on the fan coil unit. This is for either heating or cooling depending on the
heating/cooling operating type.
Signal value: 0…100%
Room: Fan coil unit, fan speed
Analog value
% (98)
1.0
The module has this BACnet output object if any option except None is selected for the Fan coil unit parameter.
Outputs the current fan speed.
Signal value: 0…100%