ABB i-bus
®
KNX
Parameters
220 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Object type
Unit
COV send
condition
Room: Operating mode override (slave)
Positive integer
value
No unit (95)
1.0
The module has this BACnet output object if the Display+set (slave) option is selected for the Operating mode parameter.
Outputs the current overridden HVAC operating mode that can be overridden by a higher operating mode.
Signal value: 0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection
Room: Window status Binary value - -
The module has this BACnet output object if the
Yes
option is selected for the
Window status
parameter.
Outputs the window status.
Signal value:
0 = Closed
1 = Open
Room: Presence (slave)
Binary value
-
-
The module has this BACnet output object if the
Yes
option is selected for the
Presence detector
parameter.
Outputs the presence status.
Signal value:
0 = Not occupied
1 = Occupied
Room: Rel. humidity value
Analog value
% (98)
1.0
The module has this BACnet output object if the Yes option is selected for the Rel. humidity parameter.
Outputs the relative humidity.
Signal value:
0…100%