ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 219
BACnet output objects
Object name Object type Unit COV send
condition
Room: Actual room temperature
Analog value
°C (62)
1.0
Outputs the actual room temperature.
Signal value:
-273...670760 °C
Room: Room setpoint temperature Analog value °C (62) 1.0
Outputs the current room setpoint temperature.
Signal value:
-273...670760 °C
Room: Controller On/Off
Binary value
-
-
The module has this BACnet output object if the Display or Display+set (slave) option is selected for the Controller On/Off
parameter.
Outputs whether the room thermostat is switched on or off.
Signal value: 0 = Off
1 = On
Room: Heating/cooling operating type Binary value - -
The module has this BACnet output object if any option except
None
is selected for the
Heating/cooling operating type
parameter.
Outputs the current heating/cooling operating type.
Signal value:
0 = Cooling
1 = Heating
Room: Operating mode
Positive integer
value
No unit (95)
1.0
The module has this BACnet output object if any option except None is selected for the Operating mode parameter.
Outputs the current HVAC operating mode.
Signal value: 0 = Auto
1 = Comfort
2 = Standby
3 = Economy
4 = Building Protection