ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 223
condition
Room: Fan coil unit, dew point sensor
The module has this BACnet output object if any option except None is selected for the Fan coil unit parameter and the Yes
option is selected for the Fan coil unit, dew point sensor parameter.
Outputs the signal value from the dew point sensor in the fan coil unit.
Signal value: 0 = Off
1 = On
Fan coil unit, level sensor Binary value - -
The module has this BACnet output object if any option except None is selected for the Fan coil unit parameter and the Yes
option is selected for the Fan coil unit, level sensor parameter.
Outputs the signal value from the level sensor in the fan coil unit.
1 = On
Analog value
% (98)
1.0
Outputs the position of the radiator valve.
The object type for the object is dependent on the settings in the module:
• If the On/Off option is selected for the Radiator
parameter:
Object type binary value
Unit –
Send condition –
Signal value 0 = Off, 1 = On
• If the 0…100 % option is selected for the Radiator
parameter:
Object type analog value
Unit % (98)
Send condition 1.0