ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 223
Object name
Object type
Unit
COV send
condition
Room: Fan coil unit, dew point sensor
Binary value
-
-
The module has this BACnet output object if any option except None is selected for the Fan coil unit parameter and the Yes
option is selected for the Fan coil unit, dew point sensor parameter.
Outputs the signal value from the dew point sensor in the fan coil unit.
Signal value: 0 = Off
1 = On
Fan coil unit, level sensor Binary value - -
The module has this BACnet output object if any option except None is selected for the Fan coil unit parameter and the Yes
option is selected for the Fan coil unit, level sensor parameter.
Outputs the signal value from the level sensor in the fan coil unit.
Signal value:
0 = Off
1 = On
Room: Radiator, valve
Binary value
Analog value
-
% (98)
-
1.0
Outputs the position of the radiator valve.
The object type for the object is dependent on the settings in the module:
• If the On/Off option is selected for the Radiator
parameter:
Object type binary value
Unit –
Send condition –
Signal value 0 = Off, 1 = On
• If the 0…100 % option is selected for the Radiator
parameter:
Object type analog value
Unit % (98)
Send condition 1.0
Signal value 0…100 %

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals