AC/S 1.x.1 | 2CDC508198D0211 Rev. A 267
Pump B operating status (Off/On) DPT 1.011
The module has this output socket if the
Yes
option is selected for the
Double pump
Yes
for the Pump display operating status parameter.
Outputs the operating status (Off/On) provided by the second pump. On pumps with their own control, this operating status
can differ from the operating status of the heating distribution circuit controller.
.
1 = Active
The module has this output socket if the Yes option is selected for the Double pump parameter.
Outputs the status of the second pump from the heating distribution circuit controller.
1 = On
The module has this output socket if the Yes option is selected for the Double pump parameter and the Yes option is selected
for the Pump display pump fault status parameter.
Outputs the fault status provided by the second pump.
Signal value: 0 = No alarm
1 = Alarm
Pump B repair switch status DPT 1.011
The module has this output socket if the Yes option is selected for the Double pump parameter and the Yes option is selected
for the Display pump repair switch status parameter.
Outputs the contact position provided by the second pump repair switch.
1 = Active