ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 279
Object name
Object type
Unit
COV send
condition
Heating distribution circuit: Room setpoint temperature Comfort
Analog value
°C (62)
1.0
This module has this BACnet output object if the Yes option is selected for the Supply temperature control parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter and the Based on
Scheduler option is selected for the Economy mode parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Comfort operating mode if this operating mode is active.
Signal value: -273...670760 °C
Heating distribution circuit: Room setpoint temperature Standby
Analog value
°C (62)
1.0
This module has this BACnet output object if the Yes option is selected for the Supply temperature control parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter, the Based on
Scheduler option is selected for the Economy mode parameter and the Yes option is selected for the Scheduler operating
mode Standby parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Standby operating mode if this operating mode is active.
Signal value: -273...670760 °C
Heating distribution circuit: Room setpoint temperature Economy
Analog value
°C (62)
1.0
This module has this BACnet output object if the Yes option is selected for the Supply temperature control parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter, the Based on
Scheduler option is selected for the Economy mode parameter and the Yes option is selected for the Scheduler operating
mode Economy parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Economy operating mode if this operating mode is active.
Signal value:
-273...670760 °C
Heating distribution circuit: Room setpoint temperature Building
Protection
Analog value
°C (62)
1.0
This module has this BACnet output object if the
Yes
option is selected for the
Supply temperature control
parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter, the Based on
Scheduler option is selected for the Building Protection mode parameter and the Yes option is selected for the Scheduler
operating mode Building Protection parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Building Protection operating mode if this operating mode is active.
Signal value: -273...670760 °C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals