ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 279
condition
Heating distribution circuit: Room setpoint temperature Comfort
This module has this BACnet output object if the Yes option is selected for the Supply temperature control parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter and the Based on
Scheduler option is selected for the Economy mode parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Comfort operating mode if this operating mode is active.
Signal value: -273...670760 °C
Heating distribution circuit: Room setpoint temperature Standby
This module has this BACnet output object if the Yes option is selected for the Supply temperature control parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter, the Based on
Scheduler option is selected for the Economy mode parameter and the Yes option is selected for the Scheduler operating
mode Standby parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Standby operating mode if this operating mode is active.
Signal value: -273...670760 °C
Heating distribution circuit: Room setpoint temperature Economy
This module has this BACnet output object if the Yes option is selected for the Supply temperature control parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter, the Based on
Scheduler option is selected for the Economy mode parameter and the Yes option is selected for the Scheduler operating
mode Economy parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Economy operating mode if this operating mode is active.
Heating distribution circuit: Room setpoint temperature Building
Protection
This module has this BACnet output object if the
Yes
option is selected for the
Supply temperature control
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter, the Based on
Scheduler option is selected for the Building Protection mode parameter and the Yes option is selected for the Scheduler
operating mode Building Protection parameter.
Outputs the room setpoint temperature that is to be used as the basis for the calculation of the supply setpoint temperature in
the Building Protection operating mode if this operating mode is active.
Signal value: -273...670760 °C