ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 283
condition
Heating distribution circuit: Pump B override disable/enable
The module has this BACnet output object if the Yes option is selected for the Double pump parameter and the Yes option is
selected for the Override by WebUI parameter.
Outputs whether the heating distribution circuit's second pump is overridden.
Signal value: 0 = Disabled
1 = Enabled
Heating distribution circuit: Pump B override value Binary value - -
The module has this BACnet output object
if the Yes option is selected for the Double pump parameter and the Yes option is
selected for the Override by WebUI parameter.
This object specifies the state with which the heating distribution circuit's second pump is overridden if the pump override is
active.
Signal value: 0 = Off
1 = On
Heating distribution circuit: Pump B operating status (Off/On)
The module has this BACnet output object if the
Yes
option is selected for the
Double pump
Yes
selected for the Pump display operating status parameter.
Outputs the operating status (Off/On) provided by the second pump. On pumps with their own control, this operating status
can differ from the operating status of the heating distribution circuit controller.
Signal value: 0 = Inactive
1 = Active
Heating distribution circuit: Pump B relay status Binary value - -
The module has this BACnet output object if the
Yes
option is selected for the
Double pump
Outputs the status of the second pump from the heating distribution circuit controller.
1 = On