ABB i-bus
®
KNX
Parameters
328 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Object type
Unit
COV send
condition
Heat generator: Pump override disable/enable
Binary value
-
-
The module has this BACnet output object if the Yes option is selected for the Override by WebUI parameter.
Outputs whether the heat generator's pump is overridden.
Signal value: 0 = Disabled
1 = Enabled
Heat generator: Pump override value
Binary value
-
-
The module has this BACnet output object if the Yes option is selected for the Override by WebUI parameter.
This object specifies the state with which the heat generator's pump is overridden if the pump override is active.
Signal value: 0 = Off
1 = On
Heat generator: Pump operating status (Off/On)
Binary value
-
-
The module has this BACnet output object if the Yes option is selected for the Pump display operating status parameter.
Outputs the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the heat generator.
Signal value:
0 = Inactive
1 = Active
Heat generator: Pump relay status
Binary value
-
-
Outputs the status of the heat generator's pump.
Signal value:
0 = Off
1 = On

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals