AC/S 1.x.1 | 2CDC508198D0211 Rev. A 395
condition
Chiller: Chiller operating status
The module has this BACnet output object if the Yes option is selected for the Show operating status parameter.
Outputs the operating status (Off/On) provided by the chiller. Due to the control integrated into the chiller, this status may differ
from the operating status specified by this module.
Signal value: 0 = Off
1 = On
Chiller: Chiller fault status Binary value - -
The module has this BACnet output object
if the Yes option is selected for the Show fault status parameter.
Outputs the fault status provided by the chiller.
Signal value: 0 = Off
1 = On
Chiller: Room control values
The module has this BACnet output object if the Yes option is selected for the Switch off if no room demand parameter.
Outputs the highest room setpoint temperature that is present on the ASM input socket and that is used by the Switch off if no
room demand function.
Chiller: Pump override disable/enable
The module has this BACnet output object if the Yes option is selected for the Override by WebUI parameter.
Outputs whether the pump for the chiller is overridden.
Signal value: 0 = Disabled
1 = Enabled