Object name
Object type
Unit
COV send
condition
Chiller: Pump override value
Binary value
-
-
The module has this BACnet output object if the Yes option is selected for the Override by WebUI parameter.
This object specifies the state with which the pump for the chiller is overridden if the pump override is active.
Signal value: 0 = Off
1 = On
Chiller: Pump operating status (Off/On)
Binary value
-
-
The module has this BACnet output object if the Yes option is selected for the Pump display operating status parameter.
Outputs the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the chiller.
Signal value:
0 = Inactive
1 = Active
Chiller: Pump relay status
Binary value
-
-
Outputs the status of the chiller's pump.
Signal value:
0 = Off
1 = On
Chiller: Pump fault
Binary value
-
-
The module has this BACnet output object if the Yes option is selected for the Pump display pump fault status parameter.
Outputs the fault status provided by the pump.
Signal value:
0 = Inactive
1 = Active
Chiller: Pump repair switch status
Binary value
-
-
The module has this BACnet output object if the Yes option is selected for the Display pump repair switch status parameter.
Outputs the contact position provided by the pump repair switch.
Signal value: 0 = Inactive
1 = Active