ABB i-bus
®
KNX
Parameters
84 2CDC508198D0211 Rev. A | AC/S 1.x.1
AND (AND)
Logical AND operator.
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
E
1
Input
Always
2
1 bit
E
2
Input
Always
3-16
1 bit
E
n
Input
Parametrizable
n = 3...16
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
A
Output
Always
An AND element can be easily inverted to a NAND element by double-clicking the output.
Parameters
Name
Value
Visible
Description
Input count
2...16
Always
Function
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
The output is 1 (true), if all inputs are 1 (true).
E
1
E
2
A
0
0
0
0
1
0
1
0
0
1
1
1
Other
Inputs not connected are treated as if they did not exist.