- 109 -
000904AG
7 - Operation
Battery
- Battery Type. Select REACT2-BATT.
- Number. Set the number of REACT2-BATT (battery unit)
installed.
Energy Policy
- Energy Policy: set the way to manage the energy produ-
ced by the PV plant, choosing from the following:
Management
mode
Description
Zero injection
The system automatically manages
SRZHUÀRZVLQRUGHUWRDYRLGWKHLQMHF-
tion of energy to the grid. If the meter is
disconnected or not working the inver-
ter’s output power is restricted to zero
in order to avoid accidental power fee-
ding to the grid.
Self consumption
The system automatically manages
SRZHUÀRZVLQRUGHUWRPD[LPLVHVHOI
consumption. All unused power from
domestic loads will feed into the grid.
Custom
The system automatically manages
SRZHU ÀRZV LQ RUGHU WR DYRLG IHHGLQJ
the grid with power greater than: PDC
x Plim
where PDC is the power of the pho-
tovoltaic generator (“PV GENERA-
TOR POWER” parameter) and Plim is
the output power limit with respect to
PDC(%) (“FEED-IN POWER” parame-
ter).
- PV Generator Power (Wp): Insert the
power value of the photovoltaic sy-
stem installed.
- Feed-in Power (% PV Generator Po-
wer): Set the percentage AC power
restriction (with reference to the value
of the photovoltaic system (kWp) in-
stalled) to be feed into the grid.
- Backup Mode:
Set the way to manage the backup funtionality, choosing from:
AUTO. The necessary condition for activating the backup
function is the lack of grid.
External Control. The backup function is controlled by an
external command.