1MAC309294-MB F Section 5
Control functions
RER620 319
Technical Manual
Shot number CBB7 0...5 0 Sets CBB7 shot number
Frq Op counter limit 0...250 0 Frequent operation counter lockout limit
Frq Op time 1...250 min 1 Frequent operation counter time
Frq Op recovery time 1...250 min 1 Frequent operation counter recovery time
Auto init 0...63 0 Defines INIT lines that are activated at auto initiation
Parameter Values (Range) Unit Step Default Description