EasyManua.ls Logo

ABB RET670 - Page 102

ABB RET670
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 14: Setting parameters for the LON communication
Parameter Range Default Unit Parameter description
DomainID 0 0 - Domain identification number
SubnetID* 0 - 255
Step: 1
0 - Subnet identification number
NodeID* 0 - 127
Step: 1
0 - Node identification number
*Can be viewed in the local HMI
Path in the local HMI under Main menu/Settings/General settings/
Communication/SLM configuration/Rear optical LON port
These parameters can only be set with the LON Network Tool (LNT).
Table 15: LON node information parameters
Parameter Range Default Unit Parameter description
NeuronID* 0 - 12 Not loaded - Neuron hardware identification
number in hexadecimal code
Location 0 - 6 No value - Location of the node
*Can be viewed in the local HMI
Path in the local HMI under Main menu/Settings/General settings/
Communication/SLM configuration/Rear optical LON port
Table 16: ADE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation
TimerClass Slow
Normal
Fast
- - Slow Timer class
Path in the local HMI under Main menu/Settings/General settings/
Communication/SLM configuration/Rear optical LON port
Table 17: LON commands
Command Command description
ServicePinMsg Command with confirmation. Transfers the node address to the LON Network Tool.
Section 10 1MRK 504 088-UEN C
Establishing connection and verifying the LON communication
96
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Related product manuals