Table 14: Setting parameters for the LON communication
Parameter Range Default Unit Parameter description
DomainID 0 0 - Domain identification number
SubnetID* 0 - 255
Step: 1
0 - Subnet identification number
NodeID* 0 - 127
Step: 1
0 - Node identification number
*Can be viewed in the local HMI
Path in the local HMI under Main menu/Settings/General settings/
Communication/SLM configuration/Rear optical LON port
These parameters can only be set with the LON Network Tool (LNT).
Table 15: LON node information parameters
Parameter Range Default Unit Parameter description
NeuronID* 0 - 12 Not loaded - Neuron hardware identification
number in hexadecimal code
Location 0 - 6 No value - Location of the node
*Can be viewed in the local HMI
Path in the local HMI under Main menu/Settings/General settings/
Communication/SLM configuration/Rear optical LON port
Table 16: ADE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation
TimerClass Slow
Normal
Fast
- - Slow Timer class
Path in the local HMI under Main menu/Settings/General settings/
Communication/SLM configuration/Rear optical LON port
Table 17: LON commands
Command Command description
ServicePinMsg Command with confirmation. Transfers the node address to the LON Network Tool.
Section 10 1MRK 504 088-UEN C
Establishing connection and verifying the LON communication
96
Installation and commissioning manual