Checking the re-trip with current check,
RetripMode
=
CB Pos Check
1. Set RetripMode = CB Pos Check.
2. Apply the fault condition, including start of CCRBRF, well above the set
current value.
3. Verify that re-trip is achieved after set time t1 and back-up trip after time t2
4. Apply the fault condition, including start of CCRBRF, with current below set
current value.
5. Verify that no re-trip, and no back-up trip is obtained.
6. Disconnect AC and START input signals.
Checking re-trip without current check,
RetripMode
=
No CBPos Check
1. Set RetripMode = No CBPos Check.
2. Apply the fault condition, including start of CCRBRF, well above the set
current value.
3. Verify that re-trip is achieved after set time t1, and back-up trip after time t2.
4. Apply the fault condition, including start of CCRBRF, with current below set
current value.
5. Verify that re-trip is achieved after set time t1, but no back-up trip is obtained.
6. Disconnect AC and START input signals.
13.6.7.5 Verifying the back-up trip mode
In the cases below it is assumed that FunctionMode = Current is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1. Apply the fault condition, including start of CCRBRF, with phase current
well above set value IP.
2. Arrange switching the current off, with a margin before back-up trip time, t2.
It may be made at issue of re-trip command.
3. Check that re-trip is achieved, if selected, but no back-up trip.
4. Disconnect AC and START input signals.
The normal mode BuTripMode = 1 out of 3 should have been verified in the tests
above. In applicable cases the modes 1 out of 4 and 2 out of 4 can be checked.
Choose the mode below, which corresponds to the actual case.
Checking the case
BuTripMode
=
1 out of 4
It is assumed that the earth-fault current setting IN> is below phase current setting
IP>.
Section 13 1MRK 504 088-UEN C
Verifying settings by secondary injection
148
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals