Ethernet port (RJ-45) on the front. The PCM600 software package must be
installed in the PC.
Disturbance upload can be performed by the use of PCM600 or by any third party
tool with IEC 61850 protocol. Reports can automatically be generated from
PCM600. Disturbance files can be analyzed by any tool reading Comtrade
formatted disturbance files.
13.2.7.4 Event recorder (ER) and Event list (EL)
The result from the event recorder and event list can be viewed on the local HMI
or, after upload, in PCM600 as follows:
1. on the local HMI under Main menu/Events, or in more details via
2. the Event Viewer in PCM600.
The internal FIFO register of all events will appear when the event viewer is
launched.
When the IED is brought into normal service it is recommended to delete all events
resulting from commissioning tests to avoid confusion in future fault analysis. All
event in the IED can be cleared in the local HMI under Main Menu//Reset/Reset
internal event list or Main menu/Reset/Reset process event list. It is not possible
to clear the event lists from PCM600.
When testing binary inputs, the event list (EL) might be used instead. No uploading
or analyzing of registrations is then needed since the event list keeps running,
independent of start of disturbance registration.
13.2.8 Identifying the function to test in the technical reference
manual
Use the technical reference manual (to identify function blocks, logic diagrams,
input and output signals, setting parameters and technical data.
13.2.9 Exit test mode
The following procedure is used to return to normal operation.
Procedure
1. Navigate to the test mode folder.
2. Change the 'On' setting to 'Off'. Press the 'E' key and the left arrow key.
3. Answer 'YES', press the 'E' key and exit the menus.
Section 13 1MRK 504 088-UEN C
Verifying settings by secondary injection
112
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals