Section 5 Installing the IED
About this chapter
This chapter describes how to install the IED.
5.1
Overview
The mechanical and electrical environmental conditions at the installation site must
be within the limits described in the IED technical data. Dusty, damp places, places
susceptible to rapid temperature variations, powerful vibrations and shocks, surge
voltages of high amplitude and fast rise time, strong induced magnetic fields or
similar extreme conditions should be avoided.
Sufficient space must be available in front of and at the rear of the IED to allow
access for maintenance and future modifications. Flush mounted IEDs should be
mounted so that IED modules can be added and replaced without excessive
dismantling.
1MRK 504 088-UEN C Section 5
Installing the IED
23
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24