See section "Flush mounting dimensions" regarding dimensions.
2. Carefully press the sealing strip (1) around the IEDs collar. Cut the end of the
sealing strip a few mm to long to make the joining point (5) tight.
The sealing strip is delivered with the mounting kit. The strip is long enough
for the largest available IED.
3. Insert the IED into the opening (cut-out) in the panel.
4. Add and lock the fasteners (2) to the IED.
Thread a fastener into the groove at the back end of the IED. Insert and
lightly fasten the locking screw (4). Next, thread a fastener on the other side
of the IED, and lightly fasten its locking screw. Lock the front end of the
fastener in the panel, using the M5x25 screws.
Repeat the procedure with the remaining two fasteners.
5.3.3 19” panel rack mounting
5.3.3.1 Overview
All IED sizes can be mounted in a standard 19” cubicle rack by using the for each
size suited mounting kit which consists of two mounting angles and fastening
screws for the angles.
The mounting angles are reversible which enables mounting of IED size 1/2 x 19”
or 3/4 x 19” either to the left or right side of the cubicle.
Please note that the separately ordered rack mounting kit for side-by-
side mounted IEDs, or IEDs together with RHGS cases, is to be
selected so that the total size equals 19”.
When mounting the mounting angles, be sure to use screws that
follows the recommended dimensions. Using screws with other
dimensions than the original may damage the PCBs inside the IED.
Section 5 1MRK 504 088-UEN C
Installing the IED
34
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals