Use the configuration tools in PCM600 to verify that the IED has the expected
configuration. A new configuration is done with the application configuration tool.
The binary outputs can be selected from a signal list where the signals are grouped
under their function names. It is also possible to specify a user-defined name for
each input and output signal.
Each function included in the IED has several setting parameters, which have to be
set in order to make the IED behave as intended. A factory default value is
provided for each parameter. A setting file can be prepared using the Parameter
Setting tool, which is available in PCM600.
All settings can be
Entered manually through the local HMI.
Written from a PC, either locally or remotely using SMS/SCS. Front or rear
port communication has to be established before the settings can be written.
12.2 Entering settings through the local HMI
Procedure
1. Set each function included in the IED in the local HMI.
2. Browse to the function to be set and enter the appropriate value.
3. Find the parameters for each function in the local HMI
The operator's manual is structured in a similar way to the local HMI and provides
a detailed guide to the use of the local HMI including paths in the menu structure
and brief explanations of most settings and measurements. See the technical
reference manual for a complete list of setting parameters for each function. Some
of the included functions may not be used. In this case the user can set the
parameter Operation = Off to disable the function.
12.3 Configuring analog CT inputs
The analog input channels must be configured to get correct measurement results
as well as correct protection functionality. Because all protection algorithms in the
IED utilize the primary system quantities, it is extremely important to make sure
that connected current transformer settings are done properly. These data are
calculated by the system engineer and normally set by the commissioner from the
local HMI or from the SMS.
The analog inputs on the transformer input module are dimensioned for either 1A
or 5A. Each transformer input module has a unique combination of current and
voltage inputs. Make sure the input current rating is correct and that it matches the
order documentation.
Section 12 1MRK 504 088-UEN C
Configuring the IED and changing settings
102
Installation and commissioning manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24